SUNBCL-11:NE3400 Intelligent Powerline Modem for PV-Plant Monitoring Issue 1.1User Manual Sunny Boy Control Light
Sunny Boy Control Light Chapter 1: Introduction SUNBCL-11:NE - 10 - SMA Regelsysteme GmbH 1.2 Normal Operation The Sunny Boy Control Light has no
Sunny Boy Control Light Chapter 1: Introduction SUNBCL-11:NE - 11 - SMA Regelsysteme GmbH 1.4 Usage of the Sunny Boy Control Light The operation
Sunny Boy Control Light Chapter 1: Introduction SUNBCL-11:NE - 12 - SMA Regelsysteme GmbH Display-Contrast Independent from the selected menu: C
Sunny Boy Control Light Chapter 1: Introduction SUNBCL-11:NE - 13 - SMA Regelsysteme GmbH Edit mode The edit mode enables modifications of specif
Sunny Boy Control Light Chapter 2: Commissioning the Sunny Boy Control Light SUNBCL-11:NE - 14 - SMA Regelsysteme GmbH 2 Commissioning the Sunny B
Sunny Boy Control Light Chapter 2: Commissioning the Sunny Boy Control Light SUNBCL-11:NE - 15 - SMA Regelsysteme GmbH The initialization phase is
Sunny Boy Control Light Chapter 2: Commissioning the Sunny Boy Control Light SUNBCL-11:NE - 16 - SMA Regelsysteme GmbH Choose the language with the
Sunny Boy Control Light Chapter 2: Commissioning the Sunny Boy Control Light SUNBCL-11:NE - 17 - SMA Regelsysteme GmbH The electricity facilities i
Sunny Boy Control Light Chapter 2: Commissioning the Sunny Boy Control Light SUNBCL-11:NE - 18 - SMA Regelsysteme GmbH Automatic Device Detection S
Sunny Boy Control Light Chapter 2: Commissioning the Sunny Boy Control Light SUNBCL-11:NE - 19 - SMA Regelsysteme GmbH [ DETECTION ] new xx
Sunny Boy Control Light User Manual SUNBCL-11:NE - 2 - SMA Regelsysteme GmbH Alteration Review Document-Number SUNBCL Issue and Alteration Revi
Sunny Boy Control Light Chapter 3: Installing of the connectors SUNBCL-11:NE - 20 - SMA Regelsysteme GmbH 3 Installation of the Connectors In t
Sunny Boy Control Light Chapter 3: Installing of the connectors SUNBCL-11:NE - 21 - SMA Regelsysteme GmbH The PC is connected via RS232 with a P
Sunny Boy Control Light Chapter 3: Installing of the connectors SUNBCL-11:NE - 22 - SMA Regelsysteme GmbH <>: These pins are connected to
Sunny Boy Control Light Chapter 3: Installing of the connectors SUNBCL-11:NE - 23 - SMA Regelsysteme GmbH PIN123456789DSUB9-SocketPIN1234567825:
Sunny Boy Control Light Chapter 3: Installing of the connectors SUNBCL-11:NE - 24 - SMA Regelsysteme GmbH Serial RS232 Cable DSUB9<>DSUB9
Sunny Boy Control Light Chapter 3: Installing of the connectors SUNBCL-11:NE - 25 - SMA Regelsysteme GmbH The cable for connecting the modem mu
Sunny Boy Control Light Chapter 3: Installing of the connectors SUNBCL-11:NE - 26 - SMA Regelsysteme GmbH • Siebert (PV-plant display or series
Sunny Boy Control Light Chapter 3: Installing of the connectors SUNBCL-11:NE - 27 - SMA Regelsysteme GmbH RS 232max. 3 to 5EnergieComDisplaysSun
Sunny Boy Control Light Chapter 3: Installing of the connectors SUNBCL-11:NE - 28 - SMA Regelsysteme GmbH PIN123456789DSUB9-Socket DSUB9-SocketP
Sunny Boy Control Light Chapter 4: Working with the Sunny Boy Control Light SUNBCL-11:NE - 29 - SMA Regelsysteme GmbH 4 Working with the Sunny Boy
Sunny Boy Control Light User Manual SUNBCL-11:NE - 3 - SMA Regelsysteme GmbH SMA Regelsysteme GmbH Hannoversche Straße 1-5 D-34266 Niestetal
Sunny Boy Control Light Chapter 4: Working with the Sunny Boy Control Light SUNBCL-11:NE - 30 - SMA Regelsysteme GmbH [ ONLINE-INFO ] Cyclic disp
Sunny Boy Control Light Chapter 4: Working with the Sunny Boy Control Light SUNBCL-11:NE - 31 - SMA Regelsysteme GmbH 4.2 Online Info Online Info i
Sunny Boy Control Light Chapter 4: Working with the Sunny Boy Control Light SUNBCL-11:NE - 32 - SMA Regelsysteme GmbH 4.3 Main Menu You may selec
Sunny Boy Control Light Chapter 4: Working with the Sunny Boy Control Light SUNBCL-11:NE - 33 - SMA Regelsysteme GmbH The Sunny Boy Control Light
Sunny Boy Control Light Chapter 4: Working with the Sunny Boy Control Light SUNBCL-11:NE - 34 - SMA Regelsysteme GmbH 4.3.3 Daily Yield The daily e
Sunny Boy Control Light Chapter 4: Working with the Sunny Boy Control Light SUNBCL-11:NE - 35 - SMA Regelsysteme GmbH 4.3.4 Events The Sunny Boy C
Sunny Boy Control Light Chapter 4: Working with the Sunny Boy Control Light SUNBCL-11:NE - 36 - SMA Regelsysteme GmbH All events with a " &qu
Sunny Boy Control Light Chapter 5: Menu Functions for Configuration SUNBCL-11:NE - 37 - SMA Regelsysteme GmbH 5 Menu Functions for Configuration T
Sunny Boy Control Light Chapter 5: Menu Functions for Configuration SUNBCL-11:NE - 38 - SMA Regelsysteme GmbH 5.2 System The menu "Setup-Syste
Sunny Boy Control Light Chapter 5: Menu Functions for Configuration SUNBCL-11:NE - 39 - SMA Regelsysteme GmbH "Memory FunctionMemory FunctionM
Sunny Boy Control Light User Manual SUNBCL-11:NE - 4 - SMA Regelsysteme GmbH Explanation of Symbols used in this Document To enable optimal usag
Sunny Boy Control Light Chapter 5: Menu Functions for Configuration SUNBCL-11:NE - 40 - SMA Regelsysteme GmbH 5.2.3 Online-Info The Message ‘Channe
Sunny Boy Control Light Chapter 5: Menu Functions for Configuration SUNBCL-11:NE - 41 - SMA Regelsysteme GmbH 5.3 Interfaces [ INTERFACES ] C
Sunny Boy Control Light Chapter 5: Menu Functions for Configuration SUNBCL-11:NE - 42 - SMA Regelsysteme GmbH detected and turn the Sunny Boy Contr
Sunny Boy Control Light Chapter 5: Menu Functions for Configuration SUNBCL-11:NE - 43 - SMA Regelsysteme GmbH [ MODEM-TEST ] Init1OK
Sunny Boy Control Light Chapter 5: Menu Functions for Configuration SUNBCL-11:NE - 44 - SMA Regelsysteme GmbH The channel selection and the numeri
Sunny Boy Control Light Chapter 5: Menu Functions for Configuration SUNBCL-11:NE - 45 - SMA Regelsysteme GmbH [ EXT. DISPLAY ] Interface C
Sunny Boy Control Light Chapter 5: Menu Functions for Configuration SUNBCL-11:NE - 46 - SMA Regelsysteme GmbH • The number left of the decimal poi
Sunny Boy Control Light Chapter 5: Menu Functions for Configuration SUNBCL-11:NE - 47 - SMA Regelsysteme GmbH configured. [ESC] leaves the menu. Al
Sunny Boy Control Light Chapter 5: Menu Functions for Configuration SUNBCL-11:NE - 48 - SMA Regelsysteme GmbH Definition of the decimal point with
Sunny Boy Control Light Chapter 5: Menu Functions for Configuration SUNBCL-11:NE - 49 - SMA Regelsysteme GmbH DATALITE The Sunny Boy Control Light
Sunny Boy Control Light Content SUNBCL-11:NE - 5 - SMA Regelsysteme GmbH Content 1 Introduction ...
Sunny Boy Control Light Chapter 5: Menu Functions for Configuration SUNBCL-11:NE - 50 - SMA Regelsysteme GmbH there is no connection to the Sunny B
Sunny Boy Control Light Chapter 5: Menu Functions for Configuration SUNBCL-11:NE - 51 - SMA Regelsysteme GmbH Example DATALITE Display Telegram
Sunny Boy Control Light Chapter 5: Menu Functions for Configuration SUNBCL-11:NE - 52 - SMA Regelsysteme GmbH 5.4 PV-Plant - Setup [ PV-Plant
Sunny Boy Control Light Chapter 5: Menu Functions for Configuration SUNBCL-11:NE - 53 - SMA Regelsysteme GmbH Device ID You may modify the device r
Sunny Boy Control Light Chapter 5: Menu Functions for Configuration SUNBCL-11:NE - 54 - SMA Regelsysteme GmbH • Separation from another plant Yo
Sunny Boy Control Light Chapter 5: Menu Functions for Configuration SUNBCL-11:NE - 55 - SMA Regelsysteme GmbH Please compare the serial numbers of
Sunny Boy Control Light Chapter 5: Menu Functions for Configuration SUNBCL-11:NE - 56 - SMA Regelsysteme GmbH • [[[[ESC]]]] cancels the detection
Sunny Boy Control Light Chapter 5: Menu Functions for Configuration SUNBCL-11:NE - 57 - SMA Regelsysteme GmbH 5.4.4 Adding a New Device If you wan
Sunny Boy Control Light Chapter 5: Menu Functions for Configuration SUNBCL-11:NE - 58 - SMA Regelsysteme GmbH [ TOLERANCES ] Warnings
Sunny Boy Control Light Chapter 5: Menu Functions for Configuration SUNBCL-11:NE - 59 - SMA Regelsysteme GmbH Device Yield Warning Remarks A 2,2
Sunny Boy Control Light Content SUNBCL-11:NE - 6 - SMA Regelsysteme GmbH 4.3.1 Total Plant...
Sunny Boy Control Light Chapter 5: Menu Functions for Configuration SUNBCL-11:NE - 60 - SMA Regelsysteme GmbH [ FAX-Info ] FAX-Info de
Sunny Boy Control Light Chapter 5: Menu Functions for Configuration SUNBCL-11:NE - 61 - SMA Regelsysteme GmbH "Company/Name": Two lines a
Sunny Boy Control Light Chapter 5: Menu Functions for Configuration SUNBCL-11:NE - 62 - SMA Regelsysteme GmbH The test fax looks like this: Fig. 5
Sunny Boy Control Light Chapter 5: Menu Functions for Configuration SUNBCL-11:NE - 63 - SMA Regelsysteme GmbH
Sunny Boy Control Light Chapter 5: Menu Functions for Configuration SUNBCL-11:NE - 64 - SMA Regelsysteme GmbH 5.6 Diagnosis The "DiagnosisDiag
Sunny Boy Control Light Chapter 5: Menu Functions for Configuration SUNBCL-11:NE - 65 - SMA Regelsysteme GmbH [01:REPORT ] ß Device ID, Report
Sunny Boy Control Light Chapter 6: PC and Sunny Data Control SUNBCL-11:NE - 66 - SMA Regelsysteme GmbH 6 PC and Sunny Data Control The Windows(T
Sunny Boy Control Light Chapter 6: PC and Sunny Data Control SUNBCL-11:NE - 67 - SMA Regelsysteme GmbH You may acquire and evaluate the data (dai
Sunny Boy Control Light Chapter 6: PC and Sunny Data Control SUNBCL-11:NE - 68 - SMA Regelsysteme GmbH Parameter Entry Description MO_Modem-In
Sunny Boy Control Light Chapter 7: Appendix SUNBCL-11:NE - 69 - SMA Regelsysteme GmbH 7 Appendix 7.1 Error Messages Error messages can occur, m
Sunny Boy Control Light Content SUNBCL-11:NE - 7 - SMA Regelsysteme GmbH 7 Appendix ...
Sunny Boy Control Light Chapter 7: Appendix SUNBCL-11:NE - 70 - SMA Regelsysteme GmbH Warning: "No contact since ... " [ WARNING
Sunny Boy Control Light Chapter 7: Appendix SUNBCL-11:NE - 71 - SMA Regelsysteme GmbH Error: Energy Yield xx % [ ERROR ] [03: WR700-07
Sunny Boy Control Light Chapter 7: Appendix SUNBCL-11:NE - 72 - SMA Regelsysteme GmbH the following you will find an overview on how to manage
Sunny Boy Control Light Chapter 7: Appendix SUNBCL-11:NE - 73 - SMA Regelsysteme GmbH In the following please find the most important causes fo
Sunny Boy Control Light Chapter 7: Appendix SUNBCL-11:NE - 74 - SMA Regelsysteme GmbH house electricity distributionconnection topublic gridInt
Sunny Boy Control Light Chapter 7: Appendix SUNBCL-11:NE - 75 - SMA Regelsysteme GmbH • Larger facilities: The optimal position of the phase c
Sunny Boy Control Light Chapter 7: Appendix SUNBCL-11:NE - 76 - SMA Regelsysteme GmbH Acceptable transmission depends on the isolation or elimi
Sunny Boy Control Light Chapter 7: Appendix SUNBCL-11:NE - 77 - SMA Regelsysteme GmbH Parallel-Working Mains Communication The data transmissio
Sunny Boy Control Light Chapter 7: Appendix SUNBCL-11:NE - 78 - SMA Regelsysteme GmbH house electricity distributionconnection topublic gridSun
Sunny Boy Control Light Chapter 7: Appendix SUNBCL-11:NE - 79 - SMA Regelsysteme GmbH and informs you about the transmission results so that yo
Sunny Boy Control Light Chapter 1: Introduction SUNBCL-11:NE - 8 - SMA Regelsysteme GmbH 1 Introduction Thank you very much for purchasing a Sunn
Sunny Boy Control Light Chapter 7: Appendix SUNBCL-11:NE - 80 - SMA Regelsysteme GmbH • Please connect continuously disturbing devices to a su
Sunny Boy Control Light Chapter 7: Appendix SUNBCL-11:NE - 81 - SMA Regelsysteme GmbH 7.2.3 Communication Testing the Communication The reliabi
Sunny Boy Control Light Chapter 7: Appendix SUNBCL-11:NE - 82 - SMA Regelsysteme GmbH • switch the data acquisition of Sunny Boy Control off:
Sunny Boy Control Light Chapter 7: Appendix SUNBCL-11:NE - 83 - SMA Regelsysteme GmbH The Sunny Boy Control Light constantly displays the perc
Sunny Boy Control Light Chapter 7: Appendix SUNBCL-11:NE - 84 - SMA Regelsysteme GmbH Accessories (optional): SMA No. Description • 35-
Sunny Boy Control Light Chapter 7: Appendix SUNBCL-11:NE - 85 - SMA Regelsysteme GmbH Menu "Setup"Setup"Setup"Setup…………Syst
Sunny Boy Control Light Chapter 7: Appendix SUNBCL-11:NE - 86 - SMA Regelsysteme GmbH Menu "Setup"Setup"Setup"Setup…………Inte
Sunny Boy Control Light Chapter 7: Appendix SUNBCL-11:NE - 87 - SMA Regelsysteme GmbH Menu "Setup"Setup"Setup"Setup…………Cont
Sunny Boy Control Light Chapter 7: Appendix SUNBCL-11:NE - 88 - SMA Regelsysteme GmbH 7.5 AT-Commands The commands described in the following
Sunny Boy Control Light Chapter 7: Appendix SUNBCL-11:NE - 89 - SMA Regelsysteme GmbH Description Class 2 Class 2.0 Local FAX station ID stri
Sunny Boy Control Light Chapter 1: Introduction SUNBCL-11:NE - 9 - SMA Regelsysteme GmbH 1.1 Technical Requirements Necessary for the usage of th
Sunny Boy Control Light Chapter 7: Appendix SUNBCL-11:NE - 90 - SMA Regelsysteme GmbH Conditions The device will be repaired in its fabrication
Sunny Boy Control Light Chapter 7: Appendix SUNBCL-11:NE - 91 - SMA Regelsysteme GmbH transmission failures via mains. We reserve the right to
Sunny Boy Control Light Chapter 7: Appendix SUNBCL-11:NE - 92 - SMA Regelsysteme GmbH External Display: ist EnergieCom GmbH, Stadtjägerstraße 1
Sunny Boy Control Light Chapter 7: Appendix SUNBCL-11:NE - 93 - SMA Regelsysteme GmbH 7.8 Sunny Boy Control Light Service S-Nr.: _________
Sunny Boy Control Light Chapter 7: Appendix SUNBCL-11:NE - 94 - SMA Regelsysteme GmbH Failure Description Describe your problem: Did t
Sunny Boy Control Light Chapter 7: Appendix SUNBCL-11:NE - 95 - SMA Regelsysteme GmbH 7.9 Sunny Boy Info Service If you are interested in gett
Sunny Boy Control Light Chapter 7: Appendix SUNBCL-11:NE - 96 - SMA Regelsysteme GmbH 7.10 Menu Overview [ ONLINE-INFO ] Cyclic display of inf